Two-stage Progressive Gas Burner Switches Smoothly And Accurately
Product Details:
Place of Origin: | Italy |
Brand Name: | baltur |
Certification: | CE、EAC、SGS |
Model Number: | TBL |
Payment & Shipping Terms:
Minimum Order Quantity: | 1 |
---|---|
Price: | US $999.00 |
Packaging Details: | Bulk, packaged |
Delivery Time: | 10-30 working days |
Payment Terms: | L/C, T/T, Western Union |
Supply Ability: | 100set |
Detail Information |
|||
Product Name: | Two-stage Progressive Gas Burner | Mode Of Operation: | Two Stages Of Fire Progressive |
---|---|---|---|
Power: | 60-205KW | Electrical Protection Class: | IP40 |
Highlight: | Accurate Gas Burner,Progressive Gas Burner,Two Stage Gas Burner |
Product Description
Product introduction:
Two-stage progressive burnerThe working mode of the burner is low fire-high fire, that is, the burner has two working points, that is, it can work in one stage of fire (low fire) or two stages of fire (high fire), and the switching process is more stable. Connect the electrical and thermostat to the burner and control the second stage of flame operation, or provide a connection terminal for the electronic output regulator. Independent step servo motors control the fuel and air flow respectively. The fan motor meets the European standard IE1. The standard configuration of the electrical protection level IP40.
Technical and performance characteristics:
1. Proportional adjustment operation can be performed through the automatic P.1.D regulator.
2. The mixing device can be directly removed without removing the burner from the boiler, which is convenient for maintenance.
3. The independent servo motor adjusts the air damper opening. When it is paused, the air damper automatically closes to reduce heat loss in the furnace.
4. The sliding flange matched with various boiler flanges can adjust the position of the burner extending into the boiler.
argument:
Model | TBL 85P TBL 85P DACA |
TBL 105P TBL 105P DACA |
TBL 130P TBL 130P DACA |
TBL 160P TBL 160P DACA |
TBL 210P DACA | |
Thermal power most kW Minimum kW |
850 | 1,050 | 1,300 | 1,600 | 2,100 | |
200 | 320 | 400 | 500 | 800 | ||
Operation mode | Two -stage fire | |||||
NOx emission mg/kWh | < 185 (Classe II EN 267) | |||||
Motor kW r.p.m. |
1.1 | 1.5 | 2.2 | 2.2 | 3 | |
2,800 | 2,800 | 2,800 | 2,800 | 2,800 | ||
* Consumption power kW | 1.50 | 1.90 | 2.60 | 2.60 | 3.40 | |
safety | A 400 V | 6 | 6 | 10 | 10 | 16 |
Ignition transformer | 2 x 5 kV - 30 mA - 230 V/ 50 Hz | |||||
Voltage | 3N ~ 400 V ±10%- 50Hz | |||||
Protection level | IP 40 | |||||
Flame detection | Photoresistance | |||||
** noise dBA | 73 | 75.5 | 79 | 79 | 87 | |
Weight kg | 82 | 88 | 92 | 92 | 95 | |
Maximum fuel viscosity (light oil) | 5.5 cst/20°C - 1.5° E / 20°C | |||||
Flow rate most kg/h Minimum kg/h |
71.6 | 88.5 | 109.6 | 134.9 | 177 | |
16.9 | 27 | 33.7 | 42.2 | 67.4 |
FAQ:
Q1: How can you get the best price quickly?
1.We need to know the boiler capacity, the fuel you plan to use and the steam pressure you need, and then we can confirm the boiler model.
2. Customer needs to provide us your name, email address and company name, and then we will send you price list immediately.And if you use whatsapp, skype or wechat, you can provide us your ID, it will be more convenient for our communication.
Q2:Why choose us?
1.40+ years of boiler manufacturing experience, 10 years of export experience.A grade boiler factory.
2.Free replacement of parts for one year, lifetime maintenance of the main engine, except for improper operation.
Q3: Details of electric control cabinet
Electric control cabinet adopts PLC touch screen, display in English. It shows working condition details of boiler, such as water temperature, water pressure, exhaust gas temperature, and over-pressure alarm, etc. In addition, the cabinet is used for set up the parameter, record and analyze the operation data, etc.
Q4:What is the using life of your boiler?
1.Normally the boiler is designed for 20 years life span, but with right operation and good maintenance,the boiler can be used for 20-25 years.