Industrial Atmospheric Pressure Hot Water Boiler Full Automatic Control Efficiency Is High
Product Details:
Place of Origin: | Henan, China |
Brand Name: | TAIGUO |
Certification: | CE、EAC、SGS |
Model Number: | CWNS |
Payment & Shipping Terms:
Minimum Order Quantity: | 1 |
---|---|
Price: | US $7000.00 |
Packaging Details: | Bulk, packaged |
Delivery Time: | 20-30 working days |
Payment Terms: | L/C, T/T, Western Union |
Supply Ability: | 100set |
Detail Information |
|||
Product Name: | Atmospheric Hot Water Boiler | Rated Power: | 1.4-17.5MW |
---|---|---|---|
Rated Effluent Temperature: | 85℃ | Thermal Efficiency: | 95% |
Highlight: | High Efficiency Industrial Hot Water Boiler,Atmospheric Pressure Industrial Hot Water Boiler |
Product Description
Product introduction:
The normal pressure steam boiler adopts the wet-back structure, the corrugated furnace is the first return pass, the threaded smoke pipe constitutes the second return pass and the plain smoke pipe constitutes the third return pass. The boiler is equipped with a complete automatic control device and safety protection device, to achieve automatic water level control and low water level alarm, furnace shutdown; Steam pressure automatic control and overpressure alarm; Boiler automatic ignition, burner fire automatic regulation and flame out protection, to ensure the safe operation of the boiler.
Product advantage:
1, multi-functional safety explosion-proof device
An explosion-proof device connected with the furnace is provided on the back plate of the boiler to prevent the fuel from violent deexplosion in the furnace, release the high energy of the moment, and can automatically reset. At the same time, it has the function of fire viewing mirror and inspection channel, and makes use of the adjustment of combustion flame in operation, furnace inspection and easy maintenance.
2, the safe precipitation time is enough
The position arrangement of the combustion chamber of the boiler, the determination of the water level conforms to the national regulations, and the water level fluctuation time requirements of the international general norms and standards are strictly followed, with sufficient safe precipitation space to ensure the safe operation of the boiler.
3, boiler maintenance is convenient
The top of the boiler is provided with a manhole, and the front and back of the boiler are provided with a hand hole device, which is convenient for the inspection and cleaning of the equipment in the furnace and the bottom of the boiler.
4, front and rear smoke box seal unique
Smoke box adopts double open smoke box door, easy to open, multi-level labyrinth seal, special sealing material, good compression performance, completely prevent the leakage of smoke, can be reused.
5, water temperature, water level protection is reliable
Boiler water temperature, water level set multiple control protection, as well as ultra-smoke temperature protection, to ensure the safety of boiler operation.
Technical parameter:
Item |
WNS0.7 |
WNS1.4 |
WNS2.1 |
WNS2.8 |
WNS3.5 |
WNS4.2 |
WNS5.6 |
WNS7 |
WNS10.5 |
WNS14 |
|
Rated power (MW) |
0.7 |
1.4 |
2.1 |
2.8 |
3.5 |
4.2 |
5.6 |
7 |
10.5 |
14 |
|
Rated working pressure(Mpa) |
Atmospheric pressure/0.7/1.0 |
||||||||||
Rated effluent temperature(℃) |
85/95/117 |
||||||||||
Rated return water temperature(℃) |
60/70/70 |
||||||||||
Thermal efficiency(%) |
98 |
||||||||||
Thermal efficiency (㎡) |
35 |
53 |
77 |
107 |
127 |
198 |
212 |
272 |
358 |
448 |
|
Energy saver heating area (㎡) |
11 |
12 |
15 |
22 |
30 |
35 |
45 |
60 |
70 |
80 |
|
Suitable fuel | Natural gas/LPG/LNG/City gas/Biogas/ Diesel /Heavy Oil | ||||||||||
Fuel consum ption |
Diesel(Kg/h) | 61 | 121 | 182 | 241.5 | 302 | 362 | 485 | 612 | 905.6 | 1207.5 |
Natural gas(Nm³/h) | 70 | 140.5 | 210.6 | 283 | 351.5 | 422.4 | 563 | 705.5 | 1055 | 1408 | |
Weight(t) |
7.1 |
8.2 |
9.9 |
12.7 |
14.2 |
17.5 |
21.3 |
22 |
35.5 |
45 |
|
Maximum transport size of boiler( mm) | 3400× 1700×2100 |
4300×1900×2300 |
3900×2100×2500 |
4700×2200×2600 |
5200×2300×2700 |
5660×2400×2800 |
5900×2500×3000 |
6600×2700×3200 |
7500×3400×3600 |
7800×3700×4200 |
FAQ:
Q1: How can you get the best price quickly?
1.We need to know the boiler capacity, the fuel you plan to use and the steam pressure you need, and then we can confirm the boiler model.
2. Customer needs to provide us your name, email address and company name, and then we will send you price list immediately.And if you use whatsapp, skype or wechat, you can provide us your ID, it will be more convenient for our communication.
Q2:Why choose us?
1.40+ years of boiler manufacturing experience, 10 years of export experience.A grade boiler factory.
2.Free replacement of parts for one year, lifetime maintenance of the main engine, except for improper operation.
Q3: Details of electric control cabinet
Electric control cabinet adopts PLC touch screen, display in English. It shows working condition details of boiler, such as water temperature, water pressure, exhaust gas temperature, and over-pressure alarm, etc. In addition, the cabinet is used for set up the parameter, record and analyze the operation data, etc.
Q4:What is the using life of your boiler?
1.Normally the boiler is designed for 20 years life span, but with right operation and good maintenance,the boiler can be used for 20-25 years.